SPECIFICATIONS FOR CONSTRUCTION OF FACILITIES REQUIRED FOR THE WASHINGTON DEPOT (Sanitized)
Document Type:
Collection:
Document Number (FOIA) /ESDN (CREST):
CIA-RDP78-05327A000300070001-5
Release Decision:
RIPPUB
Original Classification:
K
Document Page Count:
23
Document Creation Date:
December 9, 2016
Document Release Date:
March 28, 2001
Sequence Number:
1
Case Number:
Publication Date:
December 4, 1953
Content Type:
REQ
File:
Attachment | Size |
---|---|
![]() | 909.06 KB |
Body:
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
A D D E N D U M N 0. 1
T 0
S P E C I F I C A T I O N S
F O R C 0 N... S T R.;. U .p,_.: P N O F
F A C I L I T I E S REQUIRnED F OR THE
W A S H I N G T O N
D E P O T
10Y3 V 1,701___tZ CE WGE
1u C ,./'.SS; dtk, :.. 3'; ! JC * ,r3 C ~ : ! TO: ' C RU I'. 1 ST.
NEXT 1z '+/ L=e :_ Mfr ?' ", W- A'- . y'
P .,i F..*. .
P1O. ?GS : A x W YE -0110 c -1. ?G CLASS-0-
REV CLAS _.tfRL V C `t D. fit/ 3' 70-3
U N I T E D S T A T E S G O V E R N M E N T
DECEMBER ?4, 1953
Paragraph numbers mentioned hereinafter refer to the original
specification, all work shall be 1thereintandcthisnadd.e dum STATINTL
STATINTL that specification, and. drawings mentioned
OPENING: Bids shall be received at
until 3:00 P.M. Standar
C.
D
25
t
,
.
,
on
ing
en ptiblicaly opened, IN LIEU OF THE date
indicated on the Invitation for Bids.
DATE AND AACKNOW GE ON THE FORM OF BID
ATTENTION TO BIDDERS: ALL BIDDERS
RECEIPT CF THIS ADDENDUM GIVING
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
Approved For Release 2001/07/1 @j I?P78-05327A000300070001-5
GLIIIr PPAL COIWDITIONS
B.20. New Paragraph: 4ORK TO b h DONE BY CONTRACTOR.--T ,e Contractor
shall execute on the site, and with his own organization, work equivalent to
at least 25 percent of the total amount of the contract price. The cost of
materials installed by skilled and unskilled labor carried on Contractor's
own payroll may be included in the 25 percent.
b-i
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
1. Delete Page D-1 in its entirety and substitute Section D, STATINTL
same subject.
2. Add: as Page 2, "U. S. Department of Labor, Decision No
dated October 19, 1953.
3. Add: as Page 3, General Services Administration Form No. 1085.
Pages D--1, 2, and 3 are attached.
Approved For Release 2001/07/16 : CIA-JiP78-05327A000300070001-5
- Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
APPLICABLE MINIMUM HOURLY RATES OF WAGES
D-1. The attached wage determination decision of the 'Secretary of
Labor specifies the minimum hourly rates of wages which-shall be paid
to' laborers and mechanics employed or working directly upon the site of
the work embraced by this specification; the rates having been determined
by the e-Secretary of Labor in accordance with the provisions of the
Davis-Bacon Law, as amended, to be the prevailing rates. for the corre-
sponding classes of laborers and mechanics employed on contracts of a
similar character in the locality.where this work is to be performed.
THESE MINIMUM HOURLY RATES OF WAGES SHALL APPLY ONLY IF THE CONTRACT IS
IN' EXCESS OF *2,000 IN AMOUNT.
D_2.' While the wage rates given in the attached decision are the min-
imum rates required to be paid during the life of the contract, it is the
responsibility of bidders to inform themselves as to local, labor condi-
tions such as the prevailing wage rates, the length of the work day and
work wgek, overtime compensation, health and welfare contributions, avail-
able labor supply, and prospective changes or adjustments of wage rates.
The Contractor shall abide by and conform to all applicable laws, Execu-
tive Orders, and rules, regulations and orders of Federal' Agencies author-
ized to pass upon and determine wage rates., No increase in the contract
price shall be allowed or authorized on account of the payment of wage
rates in excess of those listed in the attached decision.
pr3. The wage determination decision of the Secretary of Labor is at--
.tached solely for the purpose of setting forth the minimum hourly wage
rates required to be paid during the life of the contract and is not to
be accepted as a,guarantee, warranty or representation as to the wage
rates indicated. Under no circumstances shall any mistake in attaching
the appropriate wage determination decision of the Secretary of Labor and
in the wage rates set forth entitle the successful bidder to cancellation
of his bid or contract or to an.increase in the contract price or other
additional payment or recovery.
GSA-WASH d(pproved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
GSA FORM 1083
November 198a
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
SOL-in
ca-aa)
U. S..:?EPARTMENT OF LABOR
OFFICE OF THE SECRETARY
WASHINGTON
STATINTL
Date: October 19, 1953
DECISION OF THE SECRETARY
This case is before the Department of Labor pursuant to a request for a wage predetermination
as required by law applicable to the work described on the attached wage schedule.
A study has been made of wage conditions in the locality and on the basis of information assembled
by the Department of Labor the wage rates listed on the attached schedule are hereby determined by
the Secretary of Labor as the prevailing (or, in the case of the Federal Airport Act, as the minimum)
rates of wages for the described classes of labor in accordance with applicable law.
LAW REFERENCES AND SPECIAL PROVISIONS
........ !'...._.DB Davis-Bacon Act, as amended, 40 U. S. C. 276 (a) et seq.
..................FHA National Housing Act, as amended, 12 U. S. C. 1703 et seq.
.. ...............PHA Housing Act of 1949, as amended, 42 U. S. C. 1401 et seq.
..................FAA Federal Airport Act of 1946, as amended, 40 U. S. C. 1101 et seq.
..................HSC Hospital Survey and Construction Act of 1946, 42 U. S. C. 291 et seq.
..__------------ SCA School Survey and Construction Act of 1950, 20 U. S. C. 251 et seq.
-- ------- ----- CFS Defense Housing and Community Facilities and Services Act of 1951, as amended,
42 U. S. C. 15921.
......_---------- REO Reorganization Plan Number 14 of 1950, 5 U. S. C. 1332-15.
-_------------ Regulations of the Secretary of Labor, Part 5, Title 29, Subtitle A, Code of Federal
This wage determination decision and any modifications thereof during the period prior to the
stated expiration date shall be used during such period and made a part of every contract for perform-
ance of the described work as provided by applicable law and regulations of the Secretary of Labor,
and the wage rates contained in this decision, unless modified, shall be the minimum wage rates to be
paid under any such contract by contractors and subcontractors on the work.
Under the Davis-Bacon Act the contracting officer shall require that any class of laborers and
mechanics not listed in the Secretary's decision, which will be employed on the contract, shall be classi-
fied or reclassified by the contractor or subcontractor conformably to the Secretary's decision and a
report of the administrative action taken in such cases shall be transmitted by the agency to the Sec-
retary of Labor. In the event the interested parties cannot agree on the proper classification or reclassi-
fication of a particular class of laborers and mechanics to be used, the question, accompanied by the
recommendation of the contracting officer, shall be referred to the Secretary of Labor for final deter-
mination. Where classification of laborers and mechanics which were not included in the original
decision are desired under any statutes other than the Davis-Bacon Act, a supplementary wage deter-
mination shall be requested by the Agency Head.
The wage rates contained in this decision are straight hourly wage rates. In some areas manage-
ment and labor organizations in the construction industry have collectively bargained for health and
welfare fund, contributions. Such contributions are not included in wage rates determined by the
Secretary of Labor for construction projects.
By direction of the Secretary of Labor,
/s/ Stuart Rothman
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
T1~la a11r~M4dlFl.dRtr.. ~-~Ia&~?d'- o ift11' fRw ~8f~ _?o 11~ifoJlT Patwd.
~+?J'1 GSA FORM
March 1953
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
SECTION E
GENERAL REQUIREMENTS FOR MECHANICAL WORK
E?3(a). New Paragraph: All fixtures and equipment listed under the
various Items of Work shall be submitted for approval.
E.4. Insert: Line 1, "of" after "output".
Line 2, "and" after "whole".
E.6. Modification: Line 3, insert "208-volts" in lieu of "120-volts."
E.7. Modification: Line 2, Insert "have been" in lieu of "be".
E.16(a). New Paragraph: Joints in vitreous clay pipe carrying waste
from acid-proof fixtures shall be made with bituminous type joint compound
installed as recommended by the manufacturer. Joint compound shall be a type
that has been proved in use for a period of not less than five (5) years.
E.31(a). New Paragraph: All suction lines of the refrigeration unit
provided for the air-conditioning system shall be.insulated with standard cork
covering applied as recommended by the manufacturer.
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
Approved For Release 2001/07/16 : CI fTRQPl78-05327A000300070001-5
CONCRETE PAVING
(East Side)
1.5. ri.MkL dLIj,,r O1..CLvIhNTb . --Delete first sentence.
Add: Paving shall be unreinforced. Reinforce only catch basin
as noted on drawings.
1.12. Insert word "apart" after the numbers 201-011.
1.-1
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
Approved For Release 2001/07/16 : i+RLDP78-05327A000300070001-5
2-3-(b) Add: where furnished sidewall and roof covering are not load
bearing but are attached to structural framing members, such sidewall and
roof covering may be 26 gage galvanized sheets having dee-? drawn corrugations
not over 12" o.c. and 1" deep minimum. Laps of suer material shall be at
least one full corrugation with 6" end lags.
2.6. Add: Unpaved area behind vehicular shed shall be graded ,%Tith a
slope sufficient to drain accumulated water from the north toward the south
end.
2.7. Add: The structural design of this building may be revised. to
conform to stock metal buildings if the overall width and lengths, 12 feet
bent sooacings and 14'-011 height clearances are maintained. dents cilay nave
two columns in lieu of three with a cantilever roaf in. front to accommodate
stock materials. Design shall conform to Para-craph 2.3.(c) and 2.3.(d) above.
2-1
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
Approved For Release 2001/07/16 : CIA-LR P78-05327A000300070001-5
C01401 TL TRUCk UOCk, RkiPiP iLAD 0,011Y
3.5. kdd. Reinforce ramp floor with above specified metal fabric
same as dock floor.
3.16.(d) Delete first sentence.
,Lid: "Ail work shall h,;ve three coats of ;paint (first coat
may be bonderized coat) unless specified. otherwise."
3-1
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
Approved For Release 2001/07/16 : Cl PK78-05327A000300070001-5
II DUSTRI L TY?E STELE, htILDI[vGS
4:3.(c) -kdd: where furnished sidewal and roof covering are not load
bearing but are attached to structural framin members, such side-wail and
roof covering may be 26 gage galvanized sneets haviing dee-r) drawn corrugations
not over 12" o.c. and i" deep minimum. Laips of such material shall be at
least one full corrugation with 6" end la,-:)S.
4.3.(g) Delete sentence reading. "Provide a door, a steel buck and
one solid steel, two-panel door 3'-4" wide by 61-8" high, Class ti., Under-
writer's labeled, Door and buck, as located on the drawings."
In lieu of above sentence add: "Provide a metal clad, Class
Underwriter's Labeled, door on an inclined overhead track with balances.
Provide a fusible link, hardware, etc. Door shall be 3'-6" wide (opening
31-411) and. 61-61' high."
ELECTRICAL WORK
4e5: Delete in entirety and substitute the following;
GENERAL.--This work consists of providing feeders and interior
lighting for the buildings marked Item 4.
(a) WIRING METHODS.--In the Item 4 building adjacent to Item 10, the
electrical installation shall conform to all requirements of the National
Electrical Code, Article 500, Hazardous Locations, Class I, Division 2. In
the other Item 4 building, the electrical installation shall conform to all
requirements of the National Electrical Code, Article 500, Hazardous Locations,
Class III, Division 2. Minimum conductor size shall be No. 12 AWG Lighting
Fixtures and shall be 150-watt each.
(b) SWITCHING-Fixtures in each building shall be switched as a group
from one weatherproof and raintight enclosed circuit-breaker located on the
exterior of the building adjacent to the entrance. Breaker enclosure shall be
40 inches above finished grade. Breaker shall be 2P-SN, 25-ampere
20-ampere trip, 120-volt, similar and equal to Westinghouse Type MOframe,
(c) FEEDER.,--This shall be connected to the transformer bank (See
Paragraph 10,58 b) and shall be 4-wire, 3-phase, to supply above lighting and
provide for future expansion.. Form No, 8 conductors in li-inch galvanized
rigid steel conduit shall be routed down the transformer pole and underground
at a minimum depth of 24 inches to a watertight junction box mounted on the
exterior wall of the first Item 4 building. Junction box shall be mounted
directly below the lighting circuit-breaker specified in Paragraph 4.5 (b) above
and one phase of the feeder shall be connected to that breaker through a short
conduit. From this junction box, the feeder shall be continued, using identical
4-1
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
conductors and conduit, running underground at a depth of 24 inches to a
second junction box similarly, located on the exterior wall of the second
Item 4 building. One phase (other than the one used at the first building)
shall be connected to the lighting breaker through a short conduit. Ends
of all unused conductors in the second junction box shall be suitably taped
and the conductors neatly coiled for future use. Boxes shall be rain-tight
and weatherproof, 12xl2x1+ inches deep. Feeder conductors shall have
Type USE, Style,RR, insulation and covering.
4-2
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
Approved For Release 2001/07/16 : CIkPa8-05327A000300070001-5
CQWCR Th P. , VIWG
('Test bide)
6.6. sdd: Reinforce only f1oir slab under new building noted as
:item 10.
6-1
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
Approved For Release 2001/07/16 : (iy I$P78-05327A000300070001-5
INSitE STOIRAGE AREA INSTALLATIONS
8.2(a). Cmit: Last sentence of Paragraph as water and waste lines
are.specified otherwise under plumbing work.
.?3...Change: Line 3, "22" to "12".
.Add:.. At'end of Paragraph: "and the installation of water supply
and drain.lines for a.two-ton refrigeration compressor and, cooling unit.
8.3(a). Sprinkler heads shall be of approved type with nominal 2" orifice
and of ordinary degree 'temperature rating installed in pendent position below
the ceiling and spaced for extra hazard occupancy.
8.,4(a).:. For ewer connection, drainage and waste lines, etc.,. see
Paragraphs E.14. and E.20., inclusive, and E.23. to E.25., inclusive.
(b) Provide 2" funnel drain with ll" drainage pattern cast iron "P"
trap for discharge from air-conditioning unit. Discharge must be over funnel
drain with approved air gap fitting. A direct connection to drain line is
prohibited.
.(c). For. water supply piping, see Paragraphs E.21.,. E.22., Eia26., E.27.,
and E.28. of the. Specifications. .
(d),,For pipe hangers supports, off-sets, sleoves,and collars, see
Paragraphs E.32., E.33., and E.34.
(o), For pipe covering,?see Paragraphs E.29, 1$.30>, and E.31. All'cold
water supply piping shall ; be. covered:
(f) For painting, see Paragraph E.35., of the specifications.
(g) For testing, see Paragraph E.8., E.9., E.10., E.36.,. and,9.22:of
the specifications.
(h) For guarantee, see Paragraph E.37. of the specifications.
8 5? Cmit Paragraph and insert the following:.
SCOPE OF WORK.=-This part of the specification includes the
installation complete of a suspended type unit cooler in the film vault with
the refrigeration compressor on platform above the suspended ceiling. The
complete unit with the controls will be provided by the Government from a
previous installation.
8-1
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
8.6(a). New Paragraph: The unit cooler is a Carrier Unit Model 15M762
and is to be installed in the outside (S.W.) corner of the vault so as to
blow down the aisle causing acircular air motion around the vault. Cooling
unit shall be suspended by four (4) 3/8" rods from the ceiling joists, with
the bottom of unit approximately 7'-6" above the floor. Provide suitable
bridging for securing hanger rods in proper position.
'(b) The refrigeration compressor is'a Chrysler Unit Model R-160 with
2 H.P., 208-volt, three-phase motor and starter. The unit shall be mounted
on the ceiling joists above the cooling unit. Provide- a platform approxi-
mately 4'-6" constructed of 2"x6" first-grade planking to be mounted above
the ceiling joists for supporting the unit. Provide anti-vibration units
as recoffmcnded by the manufacturer for supporting the compressor on the .
platform. Provide flexible connectors in all rigid pipe and tubing connectionu
(c) Provide all necessary copper tubing and fittings, etc.., to properly
connect the cooling unit and compressor. Provide 2" copper tubing for drain
line from pan below unit cooler and extend to funnel drain as required under
plumbing work. Provide copper tubing with shut-off valve for water supply
to condenser through automatic valve with drain line to'funnel drain provided
under plumbing work. Water supply line shall be insulated, see Paragraphs E.21 Awe E.30., and 19.31.
(d) Install and adjust all controls provided for automatic temperature
control and compressor operation including all safety devices.' Room thermostat
shall operate solenoid valve in liquid refrigerant line to cooling unit.
Provide check valve in suction line to control shut-down back surge of
refrigerant.. Compressor shall operate automatically on pressure controls.
Provide secondary pressure ccntrol for emergency cut-out. All equipment
previously installed with the cooling system shall be re-installed.
(e) Unit cooler fan motor shall operate continually and will be provided
with outside switch and pilot light under electrical work. Compressor motor
shall operate automatically through pressure control and magnetic starter
as provided with the unit.
(f) Insulate suction line with coinine'rcial insulating rubber tubing or
other approved material.
8.1. Delete the words "and lights".
Insert the words "and lights" immediately following "unit".
8.9. Insert "pendant" following the word "industrial".
8.11. CIRCUITS.-- Add the following:
A.similar pilot light, except with green lamps, shall be
provided for the fan motor and shall be connected to show when the fan
motor is energized and shall be located 12 inches above the red pilot light.
Vew
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
8.15. Delete this Paragraph in its entirety and substitute the following
This work consists of removing two existing fluorescent lighting
fixtures from their present temporary mountings and install them, plus
four (4) more, as hereinafter described. Four (4) fixtures shall be
installed on a new ceiling which will be furnished by others and shall
be connected to same feeder as at present and shall be controlled in
pairs from switches located near the entrance. The remaining two (2)
fixtures shall be suspended over an adjacent storage booth and connected
to existing overhead feeder and shall. be controlled from a switch located
near the booth entrance. Armored cable, 2-wire, No. 12, may be used
throughout.
8-3
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
Approved For Release 2001/07/16I:jA-DP78-05327A000300070001-5
9.7.(b) hdde '"Meeting stiles for double doors shall be rebated."
9.10. Revision: Line 2, shall read, "installation complete of sink,
electric water heater, and water supniy".
9.15. viodificatioh`a Grater connection of 1 1/4" size, shall be made to
water maim at corner of 'building and run into building along side of sewer
line as indicated on. dravdngs.
9..16. Modified as in Paragraph 9.15, above.
9.17.(a) New Paragraph: Drain, waste,, and vent lines snail be sized
in accordance with the recommendations of the National kiumbi.ng Code.
;,9.25, add at end of paragraph: "Room conditions shall be 78 deg.
D.D.:.with 45 percent relative humidity."
9.29. Omit this nara-,rash in its entirety. (Other types of units will
not be considered under the base bid.)
9.31. t,,dd: "Paragraphs 10.33 to 10.36 inclusive.'r
IT P ^-h? Provide splitter and. volume dampers at all
r
d
F
a eW
branch connections and wherever required for balancing.; the system. Edges of
dampers shall be rieimned and covered faith felt glued on. and riveted at not
more than 6" spacing.
(b) Duct eonnecticn for 'winter heating shall be made to existing
blanked off warm air duct approximately 15 feet beyond wall No. 5-
9.34.(a) Duct lining.-The suooly duct shall be lined from the .6.C.
Unit to transition piece beyond the second diffuser in each duct line.
The return ducts -shall be 'lined. from the As . C . Unit to partitions No. 6
and No. 7 in each case.
9.Ll. Correction, Line 1, insert "maintain" in lieu of "man".
94l.(a) ..i.dd-. Provide a humidistat to maintain the desired relative
humidity. Humidistat shall be located in Room "311.
(b) Relocate existing temperature controls for the Dravo heating
Unit from their present locations to 4r all No . 4 in Room "C" at a. point
aporoxi;rnately 6 ft. from the outside wall.
.9.,45.(a) Provide a 3" cast iron -pipe funnel drain with 2" "P" trap,
below floor for over-flow and drain from the k.C. Unit and condensing unit.
Drain shall be located between the units with funnel about 6"high. Extend
drains from units into funnel'with'a-oproved air gap. it direct connection
to drain line is pronibited.
9-1
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
9.52(e). Add this sentence: "See Paragraph 9.9."
9.55. In the last sentence, the word "guys" should be "grips/"
9.55('g). New Paragraph: SPECIAL RECEPTACLES.--Contrary to the note
on Contract Drawing No. 5, these two (2) receptacles are non-existent
and shall be furnished under this contract and shall be 3-wire, 3-pole,
50-ampere, 250--volt, similar and equal to Bryant No. 3845, with No. 4786,
30-ampere cap. Associated conduit shall be 1-inch with 3 No. 10 conductors,
instead of 3i4-inch with 2 No. 10, as shown on drawing.
9.56(a) Delete this Paragraph in its entirety and substitute the
following:
a. NEW PANEL C.--This shall be a four-wire, three-phase power
distribution circuit-breaker panel, surface-mounted, connected by four (4)
No.'1/0 conductors to the line side of existing panel A. Panel C shall be
similar and equal to Westinghouse "Do-Ion" convertible type for feeder and
power distribution circuits, with breaker ratings as follows:
(1) Main - 225-ampere frame, 125-ampere trip.
(2) For 60-ampsre receptacle branches - 100-ampere frame, 70-
ampere trip (one breaker for each receptacle.)
(3) For 30-am,ccrc receptacle branches - 50-ampere frame, 35-
ampere trip (one 'o_?c.aker feeds both receptacles.)
(4) For air compressor branch - 50-ampere frame, 35-ampere
trip (one breaker).
(5) Spares - 50-ampere frame,.35-ampere trip (two breakers.)
All breakers shall be 3-pole. Total number of branch circuit-breakers is
six (6)-.
9.56(d.). Now Paragraph: AIR COMPRESSOR DISCONNECT SWITCH,--Instead
of the location shown on Contract Drawing No. 5, the air compressor dis-
connect switch shall be on the northerly wall approximately six (6) feet
from the corner.
9.57. New Paragraph: ALTERNATE BID.--The Contractor shall also submit
an alternate bid, covering the following work in lieu of the work described
under Paragraph 9.52.:
a. Furnish and install a 225-KVA transformer substation on the
roof of the warehouse, adjacent to the existing 300-KVA substation.
b~. Reroute one existing secondary feeder from existing 300-KVA
bank to the new 225-KVA bank specified above, with new circuit-breaker..
c. Install secondary feeder from above 225-KVA bank to Rooms A, B,
C, and D of area marked Item 9.
9-2
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
~ow
Approved for ~eh el 2?011/607/16teCIAnRDP78-05327A000300070001-5
Rooms A, B, C, and D of Item power and lighting system in
9 area.
e. In other rooms of Item 9 area, install power panel
and receptacles and connect two machines.
f. Grounding of expanded metal in walls Numbered 2, 5, and 6.
Work described in sub-paragraph a, b, and c shall be as specified in
Paragraphs 9.58., 9.59., and 9.60.
9.58. Now Paragraph: 225 KVA TRANSFORMER SUBSTATION.--This shall
be for transformation from 12.5/7.2 KV, 4-wire, 3-phase, to 208?120--volts,
4-wire, 3-phase, and shall consist of three (3) single-phase transformers
mounted, equipped and connected similar to the existing 300 KVA substation.
225 KVA substation shall be supported by the main interior warehouse walls
at the point of intersection, and shall have a structural steel frame,
steel pipe poles with wooden croesarms for the high voltage line, painted
wooden slat platform and railing. Necessary fused disconnect switches,
arresters, wiring, etc., shall be furnished and installed. The high-voltage
line now supplying the 300 KVA bank shall be extended to supply the 225 KVA
bank also. Transformers shall be outdoor distribution type, similar and
equal to General Electric Company "Pyranol"-filled.. Secondary conductors
shall be 750 MCM and 500 MCM for phase wires and neutral, respectively.
Outdoor-type circuit-breaker cabinet, accessible from outside the substation
platform, shall be provided and connected to the transformer secondaries.
Four (4) circuit-breakers shall be provided, all with 600-ampere frames,
two (2) with 225-ampere trip and two (2) with 300-ampere trip.
9.59. New Paragraph: REROUTE EXISTING FEEDER.--One of the secondary
feeders presently connected to the 300 KVA bank shall be rerouted so as to
be connected to a 300-ampere breaker in the breaker cabinet at the 225 KVA
bank. These existing feeders each consist of four (4) 300 MCM conductors
and the feeder to be rerouted shall be selected by the Contracting Officer.
9.60. New Paragraph: NEW SECONDARY FEEDER.--This shall and equal in all respects to the feeder specified in Paragraph 9.5L.,
except it shall be connected to a 225-ampere breaker at the 225-KVA substatior
9-3
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
Approved For Release 2001/07/12TEI \--DP78-05327A000300070001-5
INDUSTR L TYF1 STEEL BUILDII G
10.2.(k) Add: "and a gasoline storage tank."
10.3.(c) Add: Where furnished sidewall and roof covering are not load
bearing but are attached to structural framing members, such sidewall and roof
covering may be 26 gage galvanized sheets having deep drawn corrugations not
over 12" o.c. and 1" deep minimum. Laps of such material shall be at least
one full corrugation with 6" end laps.
10.3.(h) Add Provide safety chain extending to within 7 ft. of the
floor for operating dampers. Provide "catching device", and fusible link
under damper and 1" dia. rings in ends of chain. Damper snall be weighted
to close by gravity.
10.4. (f) Change Period to a comma after words "No. 10 gage".
10.6. Ladd: "Fencing at incinerator shall terminate on posts set as
Q
%aw
close as possible to metal incinerator".
10.9. Insert: "and E.5" after "L.4"?
10.19.(a) For testing, see Paragraphs E.8, L.9, L.10, L.36, and 9.22.
10.21. .dd: "and a gasoline storage tank".
10.48. kdd. Filter shall be of the replaceable cartridge type and
filter body shall have plugged ouening in bottom for draining sediment,
condensation and water, etc.
10,52. Kidd. Motor and starter shall.be explosion proof type, and fan
shall have aluminun blades.
10.53. Modification: Provide 5" exhaust pipe in lieu of 4" as specified.
ELECTRICAL WORK
10.58(d)(5) Circuit breaker rating should read: "3-pole solid neutral...
10.58e. Conduit. Add the following:
All electrical work, including light fixture, light switch,
convenience outlets, conduit, fittings, etc., in the paint room shall be
in strict accordance with Article 500, Hazardous Locations, Class I,
Division I, of the National Electrical Code.
10-58i. New Paragraph: BUILDING GROUND.--The building structure shall
be grounded by four (4) 3/4"x8' copperweld ground rods driven in the ground,
one at each outside corner of the building and connected to the steel wall
by a short No. 2/0 conductor. Connections shall be brazed.
10-1
Approved For Release 2001/07/16: CIA-RDP78-05327A000300070001-5
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
MEDIC.,L IND dEATH ROOKY INSLJ. ~TIONS
1:L.2. (b) Omit. Last sentence of the paragraph; as sink is specified
to be furnished under the plumbing work, la.ragraoh 11.5?(a).
ll.4. aT.,RiOR DOOR.--Delete this paragraph and add in its place:
"Cut through stud wall, plaster board covered and''install a wood frame
and wood door where indicated on drawings. Door to be 31-6" wide by 7'-0"
high' by l 3/4" thick' and of a solid two-panel type. Complete hardware
including three butt hinges and a cylinder type lock shall be installed..
Case no both sides and to with 1".x5" square edge casing."
11.5.(a) New .Paragraph: PLUrmBl G FIXTURES shall be provided as
listed below, cormplete'with'accessories, trimmings, and hangers unless
otherwise specified.
Water Closet: No. E46F (F.S.) complete with No. C1 white.
seat, without check hinge in lieu of No. CLR
seat. Provide seat bumper. Type LC flush
valve.
Lavatories : No. , VB20 20"x18" corn fete with pattern FR faucets,
trimmincs, and accessories. Figure 96 "P" trap,
17 gage seamless brass tubing.
Sink . Shall be a stainless steel fixture a-onroximately
48"x24" over-all, similar.to,.Lustertone No:
$-0818. with R.H. drainboard as manufactured by
Elkay ihianufacturing Company: Sink shall be
.provided with a stainless steel apron
arooroximately 8" deeio all supported by not less
than 3 heavy rigid galvanized angle iron
brackets securely attached to wall. Provide
chromium plated combination swing nozzle
faucet, heavy gauge waste outlet and strainer
and tall piece, and a tellurium lead hard cast
"1"' trap.
(b) See Paragraphs E.U and E.5 for specification requirement for
plumbing fixtures.
(c) Provide fixture hangers and backing, see Paragraphs E.ll,
.E,12, and E.13.
(d) Llectric Water Heater.--Furnish and install an electric
water heater of 10 gallons capacity on platform above the ceiling joists.
The single heating element shall be of 1200 watts capacity to operate on
208 volts. See Paragraph E.6 of the specifications for further details
and requirements.
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
Approved For Release 2001/07/16 : CIA-RDP78r-05327A000300070001-5
(e) For sewer connection, drainage and waste lines, etc., see
Paragraphs E.14 to E:.20 inclusive, and .23 to E.25 inclusive.
(f) For water sun ply piping, see Paragraphs E..21, L.22, L.26,
L.27, and E.28 of the specification.
(g) For pine hangers, supports, offsets, sleeves and collars.
See Parasranhs E?32,;F.33, and E.34.
(h). For pipe covering, see Paragraphs x.29, E.30, and E.31. All
cold andihot water piping shall be covered.
(i) For painting, see Paragraph E,.35?
(j) For, testing, see Paragraphs 11i.8, E.9, E.lO, h-36, and 9.22.
(k) For guarantee, see Paragraph ;..37.
ELECTRICAL WORK
11.7. Delete this Paragraph and substitute the.following:
ELECTRIC WATER HEATER.--Furnish and install,an electric water
heater of 10 gallon capacity on platform above the ceiling joists. The
single heating element shall be of 1200-watts capacity to operate on
208-volts. See Paragraph E.6. of the specifications for further details
and requirements.
11.11. Connection specified for watgr.heaters.:shott1d be "Lines 2 and
31; -
11-2
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5
ITEM 12
CHANGES IN ALARM AND &AFETY CONTROL SYSTEMS
ELECTRICAL WORK
Attention is invited to the fact that Paragraphs 12.8. to
12.13., inclusive, pertain only to the control of outside lights
as specified in Paragraph 12.7.
Approved For Release 2001/07/16 : CIA-RDP78-05327A000300070001-5